The controller is standard delivered with;
- Full manual (PDF)
-1 Temperature sensor 0-95°
-1 Microphone
-1 External antenna 3m
-1 Power supply adapter 110/260VAC 12Vdc
-T2 (-40-125), Level/Hygro sensors and
other
are optional.
The LEDs show
the
radio module initialization, any
communication
with the gsm network, the grid power
when the adapter is used and Alarm On or Off.. The reply is sent to
any mobile number sending the request or to number
N1 in
list if calling number is not recognized. The system can be setup to
automatically send daily or repetitive status messages. Items can be
added or
removed from the SMS status message. Command [0000 AL] will make SMS you the
actual input delays list and names.
The following exemples below shows; commands sent to the
controller as [bold] and
messages sent from the controller to the cell phone in green.
S General
status informations.
[Pw s] to the controller will
make it reply with
the current basic status.
R2 Off Jn
Jn (Jn
eventual Junctions). See (J?).
R3 Off Jn
(Items can
be removed from status(R4?).
R5
ON Jn
See or send [Pw
R?] for relais info's.
V1 13.5
Internal Bat Volt(T31) PowSupply
input.
V2 53.5
External Voltemeter(Terminal33)0-100V.
T1 18.2
Temperature T1 (0-95) on Terminal 39.
T2 -24.2
Temperature Thermometer 2 (-40-125)
AC=ON
RST
1
or 0 Grid (T29), 3Ph control.
G 24%
Tank (liquid)
level.
Y 56%
Hygrometer (0-100rH).
i0-7:
01101100 Inputs
Level.
A=ON M0
Alarm On/Off, Mic
On/Off, Status on call.
13:45
Controller time clock (RTC)
A Alarm
Inputs.
Display Alarm Delays.
Force Alarm.
Up to six alarm inputs can be connected. The sensor (or group of
sensors) can
be any (magnet, pressure, temp, …) switch contacts directly connected
to
the controller inputs. Any device, like motion detectors or fire alarm
sensors
with a potential free output that can make or break a circuit (between
GND and
the input) like a switch will do, can be used.
Any level CHANGE on Inputs A1 to A7 will trigger the alarm and the
emission of
an Alarm SMS after the corresponding Input Delay.
The Alarm function is standby when A=Off and is in watch when A=On or
A=O+ as
shown in the status-SMS.
The Alarm can be switched On manually with Input AE (A0) T17 to GND or
Off when
T17 is left open. Command [Pw
A On]
or [Pw A Off] can be mixed
with the
manual setting. Command [Pw A O+]
prevents the alarm to be set off with the manual switch.
AL Display Alarm
Delays.
Each alarm input A0 to 7 can have a delay assigned to it. This is the
delay
before an alarm SMS will be sent after corresponding input level
change. So [Pw A1 20 A2 500]
will assign input 1 delay to
20 and A2 to 500 seconds. Delay input A0 sets the delay in seconds to
get out
before the alarm goes from Off (standby) to On (watch) when the alarm
is
activated with input 0 (T17) to GND. Delay can be from 0 (no delay = no
alarm)
up to several minutes ex: [Pw A0
180]
will set the exit delay to 3 min. No EXIT Delay is accounted when the
Alarm is
turned On via SMS. It then immediately goes to On/Off.
1=3 A1
2=4 A2
3=1 A3
4=16 A4
5=32 A5
6=64 A6
7=1 SOS (your SOS message)
A=ON M0
04:41 (controller clock time; is added in most received
messages)
The SOS Emergency function can warn you
via SMS. Input A7 (T26) is an
emergency
input that will always send an emergency SMS no matter if the
controller is in
alarm-, watch- or standby mode. A simple push or any on/off switch can
be
connected to this emergency input.
A1 to A7 can be edited to the wanted name
so that the message becomes
more
intuitive. So, the SOS message, that can be edited to your own needs or
left as
is, could be like;
[Pw NL]
will make send back an SMS listing the first found numbers; [Pw
NL15] will make send back an SMS listing
with numbers found from position 15. ALARM!
BACKDOOR Actual names are also
listed in the delay timing SMS. Try
[Pw AL] PUMP
OFF After editing, the
Alias will be used to command any switching on the
outputs. So
choose short, meaningful and easy-to-remember output names. To switch
on the pump
for 15 minutes and the light for 1H, send command [Pw
Pump 900 Light 3600] Keep it
short to make things fast and easy. So [0000 P(1234)].
In short,
SMS; [Jnn F1
F2 F3 F4] sent
to the
controller configures a Junction. Field F1
tells what to do for the outputs for level; 1(i1-7), On(Ar,s,c + L1,2,3), and High(V,T1,2,G,Y). A Junction
warning message looks like; Junction field F3 can
first switch an output and field F4, that normally
vectors to
the list number where to send the (optional) warning can also force a
local command. Other
outputs can be switched, switching rules can be inverted, a following
junction
can be executed! See full manual for even more possibilities, info's and examples. T1 is the 0-95 degrees
delivered thermometer, T2 is the optional
digital sensor
-40 125 degrees Celcius. V1/Bat
LOW!
or HIGH! Voltage V1 will
reflect battery supply voltage at Terminal (T31)
normally a
battery or else from 8 to 16Vdc maxi can be connected to also feed the
controller via this supply input. V2, will be externally connected at
(T33),
and can measure from 0 to 100Vdc maxi. Junction
JAC settings make possible to start a backup generator on AC grid power
fail and stop it after ACpower on restore. Both start/stop can
occur
after a configurable delay from 0 to over 4mn. A humidity sensor can optionnally be
connected to
T46(-), 47(s(, 48(+) and 49(s) without mistake
or with
its plug. Always
see the connection schema before
adding or removing any wire from/to the controller. The top label of the delivered device will show
the connections. Fast configuration of
one or several controllers can be done using our free
Windows PC
program. Testing will be very easy, because SMS and PC
traffic/commands
can be
used simultaneously. Prog
interface Download, save, unzip and install... SE
SX Command for ENERGY
AnA
Force/Simulate an Alarm event trigger.
AnA: Forcing an Alarm event for test
purpose.
When the alarm is on watch, A=On or A=O+, command [Pw
AnA] to the controller will simulate
alarm input
n change and will reply with an Alarm SMS to number N1. n can
be 1 to 7.
This gives a real Alarm test for input A1 to A7, the 6 alarm inputs and
A7 the
SOS input.
N Programming
the
numbers where to send Warning, Alert, Alarm and SOS.
Up to 64 numbers can be programmed. Command [Pw
N?] will reply with an SMS that will remind you what you can do to
program
the numbers.
At least one (mobile) number needs to be programmed at position 1
because in
many cases, number n1 will be the one where the controller will send an
SMS. To
add a number to the list at position x, just send command [Pw
Nx NUMBER] ex: [0000 n1 06554422 n2
2015423214 N10
+3224561521 n,,,]
NL listing
the numbers.
1
0655520710
2 0206222240
3 +33453256333
10 10101010
15 0655520710
35 0696465498
40 0552545245
R Outputs R1 to
R5. Command
[Pw r?] gives details on the output
function.
The 5 power outputs let you remotely drive any machine or high power
equipment
with a simple SMS command . Output 1, 2 and 3 are (No/NC) and Output 4
and 5
are (NC/NO/NC). Up to 10A 250VAC 2500W can be switched*. Be careful
when
connecting high voltage to the output!
Timing up to 65500 seconds (about 18 Hours) can be added to the
command. No
timing (just: On) will make the output simply switch On until an
Off-command
arrives.
To switch an Output On or Off, send command [Pw
R1 on] or [Pw R2 off].
Multiple commands are supported in the same SMS command to the
controller; [Pw R2 on R3 off R1
On 5 R4 120 s]. An
optional trailing s will force the controller to send back an SMS that
will show
the new outputs status including timings.
To switch an output Relais On for 3mn,
send command [Pw R1 on 180].
To do so for 1 hour [Pw R1 3600].
Outputs can be given a meaningful name such as Pump, Light, Motor...
You can
Edit the Output as you like.
So if Relais R1 is Edited to Pump, command
[Pw Pump 600] will switch the
pump for 10min. [Pw Pump Off]
could stop the pump anyway, also
before de 10mns. (See E , editing the In- and Outputs for details).
R6 and R7 have digital outputs 0-5V. They only show up in status
when
used. See also HrR and Hrs to switch on
wanted time.
*DANGER: Great care is
recommended when
blindly switching any machines or devices remotely. Furthermore, the
switching
order, that normally should arrive in a few seconds, could arrive
delayed at
the controller due to a GSM network overload or any other possible or
unexpected reasons. Therefore and in general, you must really know what
you do
and always disconnect the controller outputs and power before any work
or
maintenance on the connected devices is being done.
E EA
Editing the Alarm Inputs A0-A7
To Edit Input A2 into Backdoor, send command [Pw
EA2 Backdoor] to the controller. An alarm SMS triggered by A2 will
then
show;
A2=Low(0) TRIGGER!
Or
High(1)
Delayed SSSS sec.
Corresp, input delay. See AL
i0-7: 11011111
Alarm Inputs Level.
Pw S, AL, J?, M? Suggested
commands.
Alarm SMS count
Default 5. See parameter D.
ER Editing Outputs Relais
names.
To give R1 the name PUMP, send SMS command [Pw
ER1 pump] to the controller. To Edit Output R2 to LIGHT, send
command [Pw ER2 light] and
for Rn
[Pw ERn NewName]
Actual Output names are listed in the status SMS so [Pw
s] to the controller will show the output names.
LIGHT ON 320
NewName OFF
........
M Monitor
audio. Send [Pw M?]
explains the function.
The delivered microphone can be plugged into Terminals T49 and T50 . So
if you
put some device On remotely, you can normally voice-call the controller
(the
SIM card number) and be able to listen.
[Pw M9] makes the controller
send back
a Status short message when called. To get the status message,
set
parameter M to 9 and just normally (voice) call the controller SIM
number.
P
Password (default 0000). Changing
the
password. [Pw P?] says how.
The default Password (Pw) is 0000. To
change it, send
SMS command [OldPw P(NewPW)]. The Password is 3 to 7 characters or
digits maxi
and case sensitive with no blank in it!
F Factory parameters
restore.
[Pw f?] to the controller
shows the
details.
In case of a major problem, sending [Pw
FSRA] to the controller will force restoring the controller and the
Parameters to the default factory settings. Wait 30 seconds and use
Password
0000 (4 x zero) after a Fsra command. Then
start to
program the parameters to the wanted values. Restoring the controller
and the
Parameters to the default factory settings can also be achieved with an
internal jumper.
[Pw Fz]
only
initializes/restarts the built-in radio module (the one that connects
to the
GSM network), password and parameters remains the same. This
action has
the same effect (but from a distance) as removing and re-establishing
the
controller power. The [Pw F?]
command
to the controller will send back a SMS that shows info's
on F and all relevant parameters.
H H:M
setting for
time related functions.
To set the controller time clock at 14:49 use [Pw
H 14:49].
[Pw Hs1 4 12:15 h?] Will
force a Status
SMS to N4, each day, at 12:15. This will give a good control of the
system.
[Pw Hs2 7 00:30 h?] forces a
Status SMS
to N7, each day, at 00:30 time.
See also HSM, for status SMS to N1 at time
synchron. ex: at H+10, H+60+10,,,
See HLS for status printing on the serial
output at
HH:MM and/or HLS to print on nn seconds.
See HRN to switch chosen output at HH:MM
to HH:MM
and/or HRS for n sec at HH:MM.
D Dial to n numbers for
Alarm and
SOS. [Pw d?] Shows
details +
actual values.
Programming how many numbers will receive the message for SOS and
ALARM. Parameter
Dial tells to how many numbers in list the SMS is sent.
Command [Pw D 2 5 d?] will
make the
controller send SOS-SMS to the 2 first numbers found in the numbers
list and
Alarm-SMS to the 5 first numbers found in the same number list. Numbers
found
at lower position will be served first. Following/trailing d?
optionally
returns you the new settings. (See N above to program the
numbers)
I Interval timing
on Rn . [Pw I?]
gives details. [Pw s] show the Interval
values.
Any of the 5 outputs Relais can be used
for Interval
timer up to 65500 seconds (>18H).
[Pw I3 40 3600] will switch
on Output
R3 for 40 seconds, wait 3600s (1H) and switch it on again for 40s.
Again and
again until command [Pw I3 0]
or other
Interval values are sent to the controller. [Pw
I1 40 3600] will use output relais 1.
J Junctions.
Ji1-7 Ar,As, Ac, L1, L2, L3, JV1, JV2,
JT1, JT2 JGL, JYg,,,
The "Junctions" functions gives you the possibility to link any
input(s) or any event (Voltage, temperature, level changes and others)
to any
output(s) or action. These Junctions, soft
but physical, add
"extended" functionality and flexibility to the controller.
The most simple one for example, can switch an output relais
On, Off or for a time laps, depending of an input change while others,
can
force an action at measured values programmable edges.
[Pw J?] explains the
principles, [Pw JL] lists the
active Junction parameters,
[Pw Jd]
lists
the junction input delays.
Field F2 for level; 0 (i1-7), Off (Ar,s,c + L1,2,3) and Low for
(V,T1,2,G,Y).
Field F3 tells which output will eventually be switched.
Field F4 tells at witch number the Warning
SMS will
eventually be
sent.
Ji1-7. For example, this simple Junction SMS command [Pw Ji3 1 0 4 2] to the controller
makes
switch outputs R4 On when input A/i 3
changes from
low to high and switches it Off when high to low (to GND) level again.
An warning
SMS is sent to number 2 from the number list.
The wanted output can be switched on, off, (here above 1=On
0=Off), switched for a time laps or left unchanged for
corresponding
event. Even more, each input has its own configurable delay for (Low to
High)
and (High to Low) level events to be awaited for before action occurs.
[Pw JAR 1 0 2 0] Makes output
Rn automatically switch Output R2 On when
the alarm
function is activated (On) and Off for the opposite. This can command
other
devices On/Off together with the Alarm mode. (As usual, one (1) blank
space character
should separate the command fields).
[Pw JAS 120 -1 5 0] will
force Relais output 5 to be switched on
for wanted time laps (2nm
here) in case an Alarm event triggers on an alarm input. So a lamp,
siren or other
could be connected to this 10A Relais
output.
[Pw JAC 0 1 3 3]
Configures the AC grid power
fail/recover function (via the
delivered
AC adaptor connected on T29-30). Relais
output 3 is
set On on grid power cut event and
switched Off on
power recovery. SMS warning
is sent to number 3 in list.
JAC to JL3 also have configurable input delays for both level
changes. So
for example we could send command [Pw JacD 60 120] to setup a delay of 2mn to wait
for before
switching R3 On in case of AC power Off and wait 1mn before switch Off
after AC
power recovery.
[Pw JL1D 0 40 JL1 -1 3600 1 10]
sets
up a Junction that will activate R1 for 1H and send warning
to N10 if
power fails
on input L1 for 40s.
[Pw JV1 11 14.5 3 1] Enables
a Junction
between the voltmeter Bt/V1(T31) and output R3. So if battery level
becomes
lower than 11.1V output R3 is switched On. R3 will be
switched
off at 14.6V. SMS to N1. Same command with JV2.
(JT1/2 LowTemperature HighTemperature RToSwitch
NPositionInList) enables a junction
between
the Thermometer sensors T1(39) or T2(T47) with output Rn. This Junction gives a simple
thermostatic control
on T1/T2 or can be used to watch some cooling device that will send an
warning
at list number N.
[JGL 10 90 0 1] Can make send an warning
at 10 and 90% level (no
switching if R=0).
[JYg 40 66 12 0]
Switches Off at 40% Humidity level and On at 66, no warning
.
Ph:
L2(T36) ON!
JUNCTION TRIGGER!
JL2 5 10 R3 N3
JL2D 10 20
R3=ON
for: 5s
Use Pw s
Pw J?, JL
07:10
* Alerts are
messages sent when the Low/High configured
Low/High edges are exceeded. They are simply setup with the
function name followed by the Low and High parameters. So for example
for V1 to 11 and 14 volt, [0000 V1 11
14] See also V2, T1, T2, GL and YG.
Warning
message
are optionally send by
the Junctions (just above) that can
switch any output. They will notify of an junction action when wanted, to
any number of the list N.
Notice that when the GXL8 SMS controller is able to send both a warning
and an Alert message for the same event. This at same or different
measured and programmed values.
The Alarm
function, when activated, will send an Alarm messages.
So except the status and info's and configuration
messages received on request, we can get three kind of messages from
the controller;
Alerts, Warnings,
and Alarms.
T Temperature Alert T1
/ T2.
[Pw T?] Shows info's.
The thermometer function can automatically send you an Alert SMS when
exceeding the low/High programmed limits. A Low/High Temperature SMS Alert
is programmable with; [Pw T1
18.4 19.8]
See also JT1/T2.
Now;
18.3
The actual temperature at sensor.
LOW
limit; 18.4 Programmed
LOW Temperature edge <
HIGH
limit; 19.8 Programmed HIGH Temperature edge >
Use
Pw T? or Pw s
Recommended info's.
V
Voltage Alerts V1 V2. [Pw
V?] shows
the function info's.
The voltmeter function can automatically send you a Alert SMS when
exceeding
lower or higher programmed limits. A Low/High VoltageSMS
Alert is programmable
with; [Pw
V1
11.2 13.4] See also JV1/V2.
Now; 11.1
The actual Voltage.
Low limit; 11.2 Programmed
LOW voltage
edge <
High limit; 13.4
Programmed
HIGH voltage edge >
Use Pw
s or V?
Recommended info's.
AC Réseau/Grid/main
power control on (T29+) (T30-). Use JAC.
The controller can be powered in two ways. By the main grid power
via an
adapter 220AC to 12Vdc (T29) and possibly a battery (T31) or any other
power
source (from 10 to 16Vdc). Advantage of a double power source is,
that if the AC grid fails,
the
controller can go on with the battery supply and will still be able to
switch an
output, send warnings and alert messages...
For a generator set control,
(no grid available) the adapter can be
plugged into the
generator
high voltage output 100 to 270VAC and its output to supply Terminal
T29+ and T30-. The 12V
generator battery will be connected to T31+ and T32-. This way,
an
alarm can be
sent may the generator high voltage fail, or if the engine stops.
When the adaptor is already busy to control the AC grid and feed the
controller, we can use another adapter plugged into the backup
generator
outlet and
connect it to L1, L2 or L3, because junctions JAC, JL1, JL2 and JL3
simply have
identical functionality. We also can use the optional 380 to 3x8VDC
adaptor that will be connected to the controller RST input. See RST
below...
For even more reliability, the engine battery can be monitored with the
controller internal Voltmeter V1 via input T31. V1 function can send an
Alert message and JV1 function switch any required device and
optionnally also send an warning, may the battery voltage gets too low
or too
high.
(see V1, JV1)
For a generator control, any input i/A1-i/A6 can be used for oil and
other
control (see Ji1-6) while output Relais Rn can start and/or stop the engine. In fact,
the
controller has enough possibilities for a full generator set control
and no
other hardware needs to be added.
The controller power supply will need about 30mA in standby mode (A On
or A Off,
with Relais Off) but sometimes current
pulses upto 1 Ampère
when transmitting. So
only adequate power supply should be connected (the delivered
stabilized
adaptor!). If On,
an output Relais take
about 20mA.
Y Humidity sensor (on
T47) [Pw Y?] shows infos and settings.
This digital sensor provide very
accurate reading
from 0.1 to 100 %. Same sensor also include a digital thermometer that
can
measure temperature from -40 to +125°C at 0,4°C accuracy. But
T2
connections can
also receive a other standard thermometer same as the 0-95 degrees
delivered
sensor.
When the sensor is connected, the funtion
HYGRO
activate as soon as the parameters are programmed send [Pw
Y?] for infos. A Low/High level
SMS Alert can be programmabed with [Pw
Yg 36.5 70]. The function can also be
automated and switch any output with JYg. See JYg above.
G Pressure sensor for tank
level measure.
[Pw G?] shows info's
and
settings.
An analogue or digital pressure sensor can be connected to the
controller. Because
the sensor type, analogue or digital (rs485), is hardware dependent, it
will
need to be chosen before setup of the system.
A Low/High level SMS Alert can be programmed with; [Pw GL 10 90.2] See also JGL.
If the Junction parameters are used to switch, like a pump that could
fill
(or empty) a tank (and optionally send a warning when doing this),
programming
Alert edges outside the Junction
range could Alerte for a system failure.
RST 3 phases main/generator
control. Use JL1, L2, L3
An effective phases control can be achieved using the optional RST
adapter,
that will transform 380VAC to about 8V, by connecting it to terminals
T35, T36
and T37. Junction L1, L2, L3 can be setup for loss of power on any of
the phase
inputs. A Status SMS will show RST when power on the 3 Ph or R0T, 0RT
or other
combinations (0 = no power on this input).
When not used as 3PH control, one or more of these inputs R, S and T
can be used
to watch any high tension in the same way as the delivered adapter,
feeding the
controller from the grid (used for JAC) with connection on T29. We can
deliver
those adapters as well.
However, a low voltage input on any of these 3
terminals, from 6 to 24Vdc, is also suitable for the same purpose. See
JL1, JL2,
JL3 for direct output action and warning messages by any changes on
these inputs.
C Run time counter and Totalizator.
Info's with [Pw
C?]
A daily run time counter and totalizator,
that can be
virtually "connected" to one of the inputs i1 to i7 or An, Ln, Vn, Tn,
G or Y, is available.
Count will occur on a defined input level. For example, if L1 is
setup as
the counter input, count happens as long as L1 is powered. If no power,
it will
stop and will count again when re-powered. Count is accurate on the
minute. Status
and info's SMS [Pw
C?] show the daily counts 0-24H and the totalizator.
Pulse Counter and Pulse totalizator. A
daily
pulses counter and totalizator can be
setup for input
6 (pulse to GND) or L3 (voltage pulse).
[Pw Cp 3] [Pw
Cp 6] Pulses are added to the daily pulses counter and added
to the totalizator at 23:59+1.
See also Command [Pw Cps 5]
which also substracts pulses from the
daily counter and subsequently
from the pulses totalizator.
The PC
program. Explainations
how to use are in de prog infos files.
The PC can do all the same that can be done with SMS, but simply
with a few
mouse
clicks from the command list. As before, also a firmware update can be
loaded
into the controller via the program. Any added custom functions are
also
available on request.
Three interface systems (hardware dependent) between controller and PC
are
available; Jumper J+5 need
to be shorted (=put the jumper in) in order to communicate
with the controller. If no comm are in use (or when finished), J+5
Jumper may be removed to save power.
- RS232 (requires our or an USB-B/RS232
cable).
- USB (requires a free driver for
PC/laptop and one A/B USB cable).
Attention! This Energy Power Meter modules should only be connected by
qualified
electricians! Any connection or manipulation to the 220/380/440 grid power or a high
tension generator presents real
danger and electrocution risks!
I1
10.4 Phase
current, Ampères (via CT).
I2
11.0 Phase
current,
Ampères
(via CT).
I3
9.9 Phase
current,
Ampères (via
CT).
U1
230 Phase
voltage, Volts (directly connected).
U2
233 Phase
voltage,
Volts (directly
connected).
U3
229 Phase
voltage,
Volts (directly
connected).
L1
382 Phase
line voltage, Volts (directly
connected).
L2
384 Phase
line voltage, Volts (directly
connected).
L3
380 Phase
line voltage, Volts (directly
connected).
P1
10000 Phase
active power Watts (internal calculation).
P2
11000 Phase
active power
Watts (internal
calculation).
P3
12000 Phase
active power
Watts (internal
calculation).
PT
30000 3
Phase total active power
Watts (internal
calculation).
FT
0.90 3
Phase total power factor (internal
calculation).
FQ
50.01 Frequency
(internal
calculation).
KW
552416.6 KWH.
99999999 maxi totalisator, can be reset via SMS.
Displayed
measured values, above and below, are only examples and not real
values. The order and quantities can differ depending on the connected
energy power meter.
Each Phase reactive,
apparent power, Phase power factor
x3 and more...
The controller
can be easily configured for an automatic emission of a Status Energy (Se)
each hour or each day (See chapter H?
and [Code Hse N HH:MM]). The direct SMS
commands
[Code se] and [Code
sx] simply immediately replies to the number that
requested the infos to the controller. The Energy Power Meter will be
connected to the SMS controller with the delivered cable.
This hightech quality Energy Power Meter can also be used stand alone.